The T. J. Snow Company, Inc. Unitrol Electronics
T. J. Snow  >  Supplies  >  Unitrol > Unitrol Water Chillers

Unitrol Water Chillers

WHY BUY UNITROL CHILLERS?

 Unitrol has since 1971 only manufactured automotive grade” chillers which come complete with features that are extra cost or not available on their line of  “commercial

3/4 Ton through 3-1/4 Ton Water Chillers

grade” chillers.  And yet the cost to you is about the same. And when you add the cost they charge as options for these features, Unitrol comes out at a lower cost.

These features are supplied at no extra cost to handle continuous operation at full capacity under the harshest of industrial conditions:

  • Automatic water refill system to keep tank full even with leaks outside chiller (not on model 8000)

  • Backflow safety kit to prevent water overflow in tank when system is shut off. Kit includes zero pressure water solenoid valve, and check valve (5-ton and larger chillers).

  • Pressure bypass water system to keep flow through evaporator above minimum requirements. Allows operation at all outside water flow rates (except model 8000 mini-chiller)

  • Washable air intake filter to keep condenser clean and maintain efficiency

  • Cleanable filter/strainer on water return prevents contaminants from reducing the efficiency of the cooling evaporator and also prolongs the life of the water pump. This component can be flushed without draining or turning off the chiller.

  • Stainless Steel “brazed plate” evaporators, mounted outside of water tank.  Because of the flow rate through this evaporator the system is self-cleaning Washable filter on air intake eliminates the need to continuously clean condenser coils. This is a major advantage when it comes time for service of the chiller.

  • Stainless Steel water pumps with ceramic seals

  • Non-metallic water tank with non-metallic and brass fittings.

    5 Ton through 10 Ton Water Chillers

  • Electronic digital temperature controller. These controllers are staged for maximum efficiency on 15-ton chiller

  • Low water flow safety system to protect refrigeration components stops the compressor if a fault occurs that could freeze the system

  • All water passage fittings are non-ferrous to prevent internal rust accumulation

  • Low pressure and High Freon safety system

  • Fault indicator lights for Freon and Low Water Flow faults

  • Ability to service or inspect chiller “hot” with all panels removed

 

Download a printable information: 

PDF Icon Chiller Brochure

PDF Icon Chiller Features

TYPICAL APPLICATIONS

  • RESISTANCE (SPOT WELDERS)
  • INDUCTION WELDERS AND FURNACES
  • MIG AND TIG WELDERS
  • HYDRAULIC FLUID COOLING
  • X-RAY AND OTHER MEDICAL EQUIPMENT
  • LASERS
  • ABRASIVE CUTTING
  • CHEMICAL AND PHARMACEUTICAL
  • FOOD AND BEVERAGE
  • LABORATORY
  • MEDICAL CHILLERS

Customizing a UNITROL Chiller: UNITROL can modify any chiller model to handle special applications such as:

  • Electrical:  380V or 575V, 50Hz frequency
  • Water Pumps: Special flow or pressure requirements
  • Dual Water Pumps: One pump for internal refrigeration, one for outside load
  • Added Cooling Loops: To chill more than one circuit (Often used for Seam Welding flood cooling)
  • Split systems to place heat-producing condenser outside of building
  • Manual water refill with sight glass to replace automatic refill system
  • Alarms and interlocking systems

Non-Refrigerated Coolers: UNITROL also manufactures non-refrigerated systems that will cool water down to as low as 5°F above room temperature. These systems include a fine-finned radiator, water tank, water pump and controls. Sizes range from nominal 24,000 BTU/Hr to 1,000,000 BUT/Hr.  Contact UNITROL sales to select the appropriate model number.

Outdoor Applications: Chillers can be ordered with outdoor kits installed for use in any ambient temperature.

Water Cooled Chillers: Standard model chillers are provided with Air Cooled Condensers. UNITROL can also provide any of our chillers with Water Cooled Condensers.

 

WATER CHILLER AND INLINE BOOSTER MASTER CHART

 

CHILLERS: These units are self-contained and include a WATER TANK and WATER PUMP. Chillers recirculate water and are considered "Closed Loop" systems.

INLINE BOOSTERS: Boosters use water supplied from an outside source and do not include a WATER TANK or WATER PUMP. Inline Boosters do not recirculate water.

Photos & More Features
Chiller Brochure in PDF Format
Chiller Features in PDF Format

 

SERIES CHILLER MODEL1 INLINE BOOSTER MODEL2 TONS BTU/HR
OUTPUT
@90ºF
KW OUTPUT @90°F FAN
HP
CHILL
AVERAGE
QTY. OF
WELDERS4
LINE VOLTAGE

INLINE BOOSTER FULL LOAD AMPS

CHILLER DIMENSIONS
APPROX. SHIPPING WEIGHT (LBS.)
FULL LOAD AMPS STANDARD
PUMP
HP1

PUMP OUTPUT GPM

WATER TANK CAP. (GAL) AUTO WATER REFILL SYSTEM

PRESSURE GAUGES

L W H
  8000 8000B 1/3 4,000 1.2 1/12 15 115/1/60 13 16 1/3 3@35psi 2 NO NO 16 26 20 150
THE "A" SERIES 8015 8015B 1/2 6,000 1.8 1/16 1 230/1/60 10 16 1 20@35psi 15 YES NO 46 28 29 425
8025 8025B 3/4 8,000 2.3 1/6 1 230/1/60 10 14 1 20@35psi 15 YES NO 46 28 29 425
8026 8026B 3/4 8,000 2.3 1/6 1 115/1/60 21 29 1 20@35psi 15 YES NO 46 28 29 425
8050 8050B 1 12,000 3.5 1/6 2 230/1/60 8 15 1 20@35psi 15 YES NO 46 28 29 435
8051 8051B 1 12,000 3.5 1/6 2 460/3/60 4 7 1 20@35psi 15 YES NO 46 28 29 435
8052 8052B 1 12,000 3.5 1/6 2 115/1/60 20 28 1 20@35psi 15 YES NO 46 28 29 435
8055 8055B 1 1/2 18,000 5.3 1/6 3 230/1/60 18 22 1 20@35psi 15 YES NO 46 28 29 455
8075 8075B 1 1/2 18,000 5.3 1/6 3 230/3/60 11 14 1 20@35psi 15 YES NO 46 28 29 455
8076 8076B 1 1/2 18,000 5.3 1/6 3 460/3/60 7 8 1 20@35psi 15 YES NO 46 28 29 455
8100 8100B 2 24,000 7 2=1/6 4 230/1/60 22 26 1 20@35psi 15 YES YES 58 28 29 525
8101 8101B 2 24,000 7 2=1/6 4 230/3/60 15 17 1 20@35psi 15 YES YES 58 28 29 525
8102 8102B 2 24,000 7 2=1/6 4 460/3/60 7 9 1 20@35psi 15 YES YES 58 28 29 525
8110 8110B 3 1/4 40,000 11.7 2=1/6 7 460/3/60 14 15 1 20@35psi 15 YES YES 58 28 29 625
8111 8111B 3 1/4 40,000 11.7 2=1/6 7 230/3/60 26 28 1 20@35psi 15 YES YES 58 28 29 625
THE "B" SERIES 8200 8200B 5 60,000 17.6 2=1/4 10 460/3/60 14 17 2 50@35psi 15 YES YES 50 52 38 1,015
8201 8201B 5 60,000 17.6 2=1/4 10 230/3/60 29 34 2 50@35psi 15 YES YES 50 52 38 1,015
8250 8250B 8 90,000 26.3 2=1/4 16 460/3/60 16 19 2 50@35psi 15 YES YES 50 52 44 1,220
8251 8251B 8 90,000 26.3 2=1/4 16 230/3/60 33 38 2 50@35psi 15 YES YES 50 52 44 1,220
8300 8300B 10 120,000 35.3 2=1/4 20 460/3/60 20 23 3 80@35psi 15 YES YES 50 52 44 1,285
8301 8301B 10 120,000 35.3 2=1/4 20 230/3/60 40 45 3 80@35psi 15 YES YES 50 52 44 1,285
THE "C" SERIES 8400 8400B 15 180,000 52.7 4=1/4 30 460/3/60 37 41 3 80@35psi 30 YES YES 1206 456 516 2,3756
8401 8401B 15 180,000 52.7 4=1/4 30 230/3/60 69 77 3 80@35psi 30 YES YES 1206 456 516 2,3756
8450 8450B 20 240,000 70.3 4=1/4 40 460/3/60 45 52 5 180@35psi 60 YES YES 1206 456 516 2,9306
8451 8451B 20 240,000 70.3 4=1/4 40 230/3/60 90 104 5 180@35psi 60 YES YES 1206 456 516 2,5306
8500 8500B 25 300,000 87.9 3=1/2 50 460/3/60 58 65 5 180@35psi 60 YES YES 130 33 51 3,070
8550R3 8550BR3 30 360,000 87.9 4=1 60 460/3/60 83 93 7 1/2 230@35psi 90 YES YES 130 33 52 3,935
8600R3 8600BR3 40 480,000 140 4=1 80 460/3/60 87 108 7 1/2 230@35psi 90 YES YES 130 33 52 4,285
8650R3 8650BR3 50 600,000 140 5=1 100 460/3/60 111 132 10 310@35psi 90 YES YES 130 33 52 4,720

NOTES:

  1. CHILLERS include a WATER TANK and WATER PUMP. Other size water pumps are available to produce higher water pressure or water flow rates.

  2. INLINE BOOSTERS use water pushed from an outside source and do not include a WATER TANK or WATER PUMP.

  3. REMOTE CONDENSER: Models ending with "R" are shipped in two pieces. The inside component contains water tank, water pump, controls, and cooling evaporator. The outdoor component contains compressor, and heat-producing condenser. Customer field installation of refrigeration piping and electrical control lines is required. Dimensions shown are for the inside components only.

  4. RESISTANCE WELDING APPLICATIONS: When used to chill resistance welders. this column is calculated to cool up to the listed quantity of 75 KVA or smaller single point spot welders under typical conditions. For other applications consult Unitrol for sizing assistance.

  5. MODEL 8000 is designed to chill one spot welder (40 KVA or smaller) or up to two 250A TIG welders. It can also be used for small laboratory processes.

  6. These Models are dual compressor systems. They are supplied in two modules, each with the dimensions shown. The total weight for the two modules is as shown on the chart.

USING UNITROL CHILLERS FOR RESISTANCE WELDING APPLICATIONS

UNITROL chillers are designed to handle a large variety of industrial water cooling applications. Over the years, UNITROL has produced a large volume of chillers for use in resistance (spot) welding applications. Our experience in sizing chillers used in welding lines allows us to provide the most economical match of chiller and application.

15 Ton through 50 Ton Water Chillers

WHY YOU NEED THE UNITROL SYSTEM FOR YOUR WELDING LINE

All UNITROL Spot Welder Chillers are self-contained, closed-loop refrigeration systems which recirculate a continuous supply of cold water virtually eliminating all water consumption. This means it's unnecessary to use city or well water which presently contaminates your water lines. So down-time for cleaning and descaling of mineral deposits is totally eliminated.

Consistent pressure and low temperature is also maintained in the cooling water, helping to reduce down-time for copper tip replacement as much as 50%. Your weld quality and uniformity is also greatly improved. The result is increased production, more efficient operation, more actual output hours. After all, it's only when your machines are running that you're turning out billable product.


UNITROL CHILLERS PAY FOR THEMSELVES IN THE FIRST YEAR

You will immediately realize an impressive increase in quality production and output hours with drastic reduction of costly tip replacement. As an example, an elimination of as little as 10 minutes per day of tip dressing represents a typical annual savings per operator of over $1,000.00. By adding the elimination of costly water, high sewer taxes, and EPA mandated water processing, you can easily realize a payback of the entire chiller cost within 5 to 12 months.

Another money saving tip: The air exhaust from the chiller can be used to heat your building, and the heat can be exhausted out during the warm months.

When you go with Unitrol, you can count on increased productivity with lower costs starting the first day of installation!

 

More information on specific Unitrol Chiller Models.
Download a printable information: 

PDF Icon Chiller Brochure

PDF Icon Chiller Features

 

Contact
Information:
6207 Jim Snow Way
P. O. Box 22847
Chattanooga, TN 37422
(423) 894-6234
1-800-NOW-SNOW
FAX (423) 892-3889
ORDER FAX (423) 490-2417
=Click to Email= welders@tjsnow.com

   Search this site       powered by FreeFind
[Service Department] [Welder Supplies] [Seminars] [Outside Sales]
[Machinery and Robotics] [Custom Design Machinery] [Remanufacturing]
[Standard Machines] [Slim Line Machines] [Transformer Department]
[Visit Us] [NEW at TJS] [Site Map] [Machine Shop